LIHCH FE180 PH120

Place of use

These cables are used in the emergency circuits as signal and communication cables, which continue functioning during an instance of fire. (They are used at places where a lot of people can be found such as subways, tunnels, shopping centers, hospitals, airports, hotels, residential buildings, industrial facilities etc.)

This type of cables is halogen-free, has flame -retarder and low smoke density.

Structure

Inner Conductor

Electrolytic Stranded Copper Wire Class 5
EN 60228, IEC 60228, VDE 0295

Insulation

Special Silicone Compound, DIN 47100 Colour Code

Stranding

Cores Twisted in Layers

Seperator

PES Tape and Glass Fiber Tape

Screen

Tinned Copper Wire Braiding

Outer Sheath

HFFR Compound EN 50290-2-27, RAL 2003 Orange

 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


LOOP
RESISTANCE
INSULATION
RESISTANCE
MUTUAL 
CAPACITANCE
OPERATING
VOLTAGE
CURRENT CARRYING 
CAPACITY
BENDING 
RADIUS
TEST VOLTAGE (50 Hz 1 Min) 
CORE/CORE
TEMPERATURE 
RANGE
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
Ω/km
79
56
39
26
19,5
13,3
7,98
MΩxKm
0,22 ve 0,34 mm² = 200
>0,50 mm² = 20
nF/km
120
V
300
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
A
2,5
4,5
6,0
13
16
20
25
7,5X D0.22 ve 0.34 mm2 = 1200 V
>0.50 mm2 = 2000 V
-40ºC+90ºC

Catalog Info