JE-HH…Bd FE180 PH120

Place of use

These cables are used in fire alarm and security systems, which continue functioning during an instance of fire. (They are used at places where a lot of people can be found such as subways, tunnels, shopping centers, hospitals, airports, hotels, residential buildings, industrial facilities etc.)


This type of cables is halogen-free, has flame -retarder and low smoke density.

Structure

Inner Conductor

Electrolytic Solid Copper Wire, Class 1
EN 60228, IEC 60228, VDE 0295

Insulation

Special Silicone Compound, VDE 0815 Colour Code

Stranding

Pairs in Layers

Seperator

PES Tape and Glass Fiber Tape

Screen

AL-PES Tape and Tinned Copper Drain Wire.

Outer Sheath

HFFR Compound EN 50290-2-27, RAL 2003 Orange

 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


LOOP
RESISTANCE
INSULATION
RESISTANCE
MUTUAL 
CAPACITANCE
OPERATING
VOLTAGE
BENDING 
RADIUS
TEST
VOLTAGE
TEMPERATURE 
RANGE
mm²
0,60
0,80
1,00
1,50
2,50
Ω/km
79
56
39
26
19,5
MΩxKm
100
nF/km
100
V
300
10X D0,6/0,8 mm : 800 V
>1,0 mm : 1000 V
-30ºC+70ºC

Catalog Info