JE-H st H…Bd

Place of use

These cables are used for in door building fittings fire alarm systems. This type of cables is halogen-free, has flame-retarder and low smoke density.

Structure

Inner Conductor

Electrolytic Solid Annealed Copper Wire,
IEC 60228, VDE 0295, Class 1

Insulation

PVC Compound, EN50290-2-21, VDE 0207:HI1
VDE 0815 Colour Code

Stranding

Pairs Stranded in Layers

Seperator

PES Tape

Screen

AL-PES Tape and Solid Tinned Copper Drain Wire

Outer Sheath

HFFR Compound, EN 50290-2-27, VDE 0207:HM2
RAL 3000 Red

 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


ÇEVRİM DİRENCİYALITIM 
DİRENCİ
EFEKTİF
KAPASİTE
ÇALIŞMA 
VOLTAJI
TEST VOLTAJIBÜKÜLME 
YARIÇAPI
ÇALIŞMA SICAKLIĞI

0,6 mm
0,8 mm
1,0 mm
1,5 mm2
2,5 mm2
Ω/km
130
73,2
44,6
24,6
14,8
MΩxKm
100
100 nF/km(Max)300 V0,6 mm ve 0,8 mm 800 V
≥ 1,0 mm 1000 V
10X D-5ºC+50ºC Hareketli
-30ºC+70ºC Sabit
ALEV GECİKTİRİCİLİK TESTİDUMAN YOĞUNLUĞU TESTİKOROZİF GAZ TESTİHALOJENSİZLİK TESTİALEV YAYILIMI TESTİ
IEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
IEC 61034-2
VDE 0482-1034-2
EN 61034-2
IEC 60754-2
VDE 0482-267-2-3
EN 50267-2-3
IEC 60754-1
VDE 0482-267-2-1
EN 50267-2-1
IEC 60332-3-24
VDE 0482-332-3-24
EN 60332-2-24

Catalog Info